HVACDirect.com Equipment Guide

How to Size a Commercial Packaged Rooftop Unit

A commercial packaged rooftop unit must match the building’s cooling and heating loads, ventilation airflow, duct resistance, electrical service, roof curb, and controls. Use this guide to understand nominal tons, estimate a preliminary capacity, and record the voltage and phase required before comparing equipment.

  • Determine the commercial cooling load
  • Match voltage, phase, airflow and heat type
  • Verify curb, duct and electrical requirements
Do not select a commercial rooftop unit from square footage alone. Occupancy, lighting, equipment, outdoor air, operating schedule, envelope, glass, orientation, climate, humidity and duct conditions can materially change the load. A qualified HVAC professional should perform an accepted commercial load calculation and verify the complete design before equipment is ordered.

Commercial Rooftop Unit Tonnage Estimator

Use a calculated design cooling load whenever available. If you only know the floor area, the square-footage method provides a broad budgeting estimate—not a final equipment selection.

Preferred: Enter a Design Cooling Load

Use the total peak cooling load from a commercial load calculation, including required outdoor air.

When entered, this result takes priority over the area estimate.

Planning Only: Estimate from Floor Area

Choose a preliminary load density. This does not account for the many inputs required by a commercial load calculation.

Record the Building Power

These choices do not calculate electrical capacity; they identify which product configuration may be compatible with the service at the unit.

nominal tons

Enter a cooling load or floor area

Your preliminary capacity will appear here automatically.

Estimated load
Nominal airflow
Selected powerNot selected

Final capacity and airflow must be selected from manufacturer performance data at the actual design conditions and external static pressure.

Shop Commercial Rooftop Units

Estimator assumptions: 12,000 BTU/h per nominal ton, common half-ton rounding for the displayed starting size, and approximately 400 CFM per nominal ton. Actual product sizes, sensible heat ratios, airflow settings and delivered capacities vary. Loads above the available single-unit range may require multiple rooftop units or a different system design.

Start with the Commercial Cooling Load

Nominal tonnage is a capacity class, not a complete description of how a unit will perform on a particular roof. Commercial load calculations evaluate the building and its use at local design conditions.

Nominal tons = design cooling load in BTU/h ÷ 12,000
Nominal sizeNominal cooling capacityApproximate starting airflow
3 tons36,000 BTU/hAbout 1,200 CFM
5 tons60,000 BTU/hAbout 2,000 CFM
7.5 tons90,000 BTU/hAbout 3,000 CFM
10 tons120,000 BTU/hAbout 4,000 CFM
12.5 tons150,000 BTU/hAbout 5,000 CFM
15 tons180,000 BTU/hAbout 6,000 CFM
20 tons240,000 BTU/hAbout 8,000 CFM
25 tons300,000 BTU/hAbout 10,000 CFM
One large building does not automatically mean one large rooftop unit. Multiple units may provide better zoning, scheduling, redundancy, duct distribution and part-load performance. The design team should divide the building into appropriate thermal zones before selecting unit quantities and sizes.

Calculate envelope loads

Include roof, walls, glass, doors, infiltration, orientation, solar exposure and local outdoor design conditions.

Add internal and ventilation loads

Account for occupants, lighting, plug loads, process equipment, required outdoor air and operating schedules.

Check actual unit performance

Verify total and sensible capacity at design temperature, airflow and altitude—not only the catalog’s nominal tonnage.

Match Voltage and Phase Exactly

Commercial rooftop equipment is offered in multiple electrical configurations. The voltage and phase at the installation point must match the complete model number and nameplate. They are not field-selectable preferences and must not be inferred from tonnage.

Common configurationWhere it may appearSelection note
208/230V, single phase, 60 HzSome smaller light-commercial packaged unitsAvailability decreases as capacity and electric heat requirements increase.
208/230V, three phase, 60 HzCommon light-commercial and commercial rooftop equipmentConfirm whether the facility service is 208V or 240V and follow the unit wiring instructions.
460V, three phase, 60 HzCommon commercial and larger rooftop equipmentUsually draws lower current than a comparable lower-voltage model, but requires a compatible 480V-class service.
208V/230V and 460V equipment are not interchangeable. A qualified electrician or contractor should measure and identify the service, confirm phase and frequency, and verify voltage imbalance, disconnecting means, grounding, conductor size and overcurrent protection. Three-phase equipment should also have correct phase sequence and protection against phase loss or reversal where required.

MCA and MOCP Are Nameplate Requirements

MCA is the minimum circuit ampacity used when sizing supply conductors. MOCP is the maximum permitted fuse or circuit-breaker rating. Neither value can be calculated reliably from nominal tons alone; compressors, indoor motors, accessories, electric heat and factory options affect the published electrical data. Use the exact unit nameplate and manufacturer tables.

Choose the Correct Packaged Unit Type

Packaged Air Conditioner

Provides cooling and may accept an electric-heat accessory. Use when a separate heating system exists or electric heat is part of the design.

Gas/Electric Rooftop Unit

Combines air conditioning with a gas furnace section. Verify gas type, supply pressure, input/output capacity, venting and combustion requirements.

Packaged Heat Pump

Provides compressor heating and cooling, often with optional auxiliary electric heat. Check low-ambient capacity and defrost requirements.

Heating must be sized separately from cooling. Gas heat is selected by rated input and output; electric heat is selected in kilowatts; heat pumps require capacity checks at the winter design temperature. Do not assume the cooling tonnage determines the correct heat size.

Airflow, Outdoor Air and Static Pressure Matter

A preliminary cooling airflow often begins near 400 CFM per nominal ton, but the correct value depends on sensible heat ratio, humidity control, supply-air temperature, ventilation, equipment limits and the duct system. The blower must deliver the required airflow against the actual external static pressure.

Supply and return ducts

Verify duct dimensions, transitions, fittings, filters, diffusers and return-air paths. An existing duct system may not support a larger replacement unit.

Outdoor ventilation air

Calculate required outdoor air for occupancy and space use. Outdoor air adds sensible and latent load and may require an economizer or powered exhaust.

External static pressure

Select the blower, motor, drive or tap that delivers design CFM at the calculated resistance without exceeding motor or unit limits.

Economizer operation

An economizer can provide outdoor-air cooling when conditions permit. Verify controls, sensors, relief or exhaust and code requirements.

Humidity and latent capacity

Restaurants, assembly areas and humid climates may need more latent performance than a simple sensible-load estimate reveals.

Altitude and ambient limits

Capacity, airflow, combustion and controls may require correction or accessories at high altitude or extreme outdoor conditions.

Replacing an Existing Rooftop Unit

Matching nominal tons is only the beginning. Photograph the entire nameplate and record the existing unit, curb and utility details before ordering.

Replacement itemWhat to verifyWhy it matters
Model and full electrical dataCapacity, voltage, phase, frequency, MCA and MOCPPrevents electrical and performance mismatches.
Roof curbOutside dimensions, opening, supply/return orientation and structural conditionDifferent brands and generations may need an engineered curb adapter.
Airflow arrangementDownflow or horizontal; supply and return locationsMust align with the duct system and selected factory configuration.
Operating weightUnit, curb adapter, accessories and service loadsThe roof structure must support the complete installation.
Heating utilitiesGas type/pressure or electric-heat circuit requirementsHeating accessories can substantially change electrical data.
ControlsThermostat, staging, economizer, BAS protocol and smoke shutdownExisting controls may not be compatible with the new sequence.
Refrigerant generationCurrent product refrigerant and associated safety provisionsNewer low-GWP equipment may require updated installation practices and controls.
Plan the lift and installation before the equipment arrives. Confirm crane access, pick weight and center of gravity, roof access, weather, rigging points, curb readiness, shutdown time, condensate drainage, service clearances and permits with qualified contractors.

Before You Select a Commercial Packaged Rooftop Unit

VerifyWhat to recordWhy it matters
Commercial design loads_____ BTU/h cooling; _____ BTU/h heatingDetermines capacity at actual design conditions.
Unit quantity and zoning_____ units serving _____ zonesAffects comfort, scheduling, redundancy and duct distribution.
Electrical service_____ volts / _____ phase / 60 HzMust match the complete model and nameplate exactly.
Exact electrical ratingsMCA _____ A; MOCP _____ AControls conductor and overcurrent-device selection.
Required airflow_____ CFM at _____ in. wgDetermines blower and drive selection.
Outdoor airflow_____ CFMAdds load and affects economizer, relief and exhaust design.
Heating type and sizeGas _____ BTU/h; electric _____ kW; heat pumpHeating load and utilities are separate selection requirements.
Curb and airflow orientationDimensions; downflow/horizontal; adapter required?Ensures physical alignment and a weather-tight installation.
Controls and accessoriesStages, economizer, VFD, BAS, smoke detector and sensorsFactory options affect compatibility, wiring and operation.

Commercial Rooftop Unit Terms to Know

Nominal ton
A capacity class equal to approximately 12,000 BTU/h of cooling.
RTU
Rooftop unit; packaged heating, cooling and air-moving equipment installed outdoors.
CFM
Cubic feet of supply, return or outdoor airflow per minute.
External static pressure
Duct-system resistance the unit blower must overcome.
MCA
Minimum circuit ampacity used to size supply conductors.
MOCP
Maximum overcurrent protection permitted for the unit.
IEER
Integrated Energy Efficiency Ratio, representing commercial cooling performance at multiple loads.
Economizer
Controls outdoor air to provide cooling when outdoor conditions are suitable.

Need Help Selecting a Commercial Rooftop Unit?

Have the design cooling and heating loads, required airflow and static pressure, voltage, phase, existing model number and curb dimensions ready. An HVACDirect.com specialist can help you compare compatible packaged rooftop equipment.

Shop Commercial Rooftop Units
Research note: Updated August 2026. The calculator is a preliminary planning tool. Final selection must follow the applicable codes, accepted commercial load calculations, manufacturer performance data, exact nameplate requirements and qualified design review.
blockboard tech