For the 36k BTU unit, is the max refrigerant pipe length is 213 ft and 98.4 ft?

Thank you for your question. Yes, the refrigerant pipe data specified in the submittal specifies a max height difference of 98’, a refrigerant pre-charge of 25’ and a max pipe length 213'. As long as the refrigerant pipe parameters are followed, there are no performance issues. The submittal can be found under product specifications on the product page. If needed, your licensed installer can adjust the refrigerant levels. For more assistance, please give us a call.