What 4 or 5 ton coils are recommended for this unit?

The G96VTN0801716A is capable of pushing up to 1600cfm of airflow. At 400cfm per ton, it can push enough airflow to properly unload 4 tons of cooling BTUs. A 4 ton evaporator coil will work perfectly fine with this.

In higher efficiency equipment combinations, you can use a 5 ton evaporator coil. However, under no circumstances can you use an outdoor condenser unit with a tonnage larger than 4. Using a 5 ton coil is perfectly fine, but if the condenser is 5+ tons then you run the risk of either your coil freezing up or allowing liquid refrigerant to travel back to the condenser's compressor which will damage the unit.

If you have any further questions, please call us and we will be happy to assist you.