What size feed is required for this unit, since the 10 KW heater draws more than 30 amps?

Per documentation indicates that the 10 kW electric heat kit requires a separate 240V electrical feed rated for 50 amps (minimum circuit ampacity), with a 60-amp maximum breaker, rather than trying to run the heater on the unit’s 30-amp cooling circuit.