Reznor UDXC 175,000 BTU Natural Gas Unit Heater, Propeller Fan, Separated Combustion Convertible - Replaces UDX-175 / UDZ-175

SAVE $1,176.00
Customer reviews
Rating:
4.9 out of 5
In Stock - 68 Ready to Ship
Free Shipping
By

Reznor

In stock
Model

UDXC-175

ID

161452

Was $3,133.00 Your Low Price Special Price $1,957.00
 
Product Features
  • 175,000 BTU heating capacity with TCORE2 titanium stabilized aluminized steel heat exchanger
  • Vibration isolated propeller fan designed for low noise operation
  • Standard power vent setup can be converted to separated combustion all in one unit
  • Certified for Commercial and Industrial applications

Introducing the new Reznor UDXC Universal, Gas-Fired Unit Heater. The Reznor model UDXC gas-fired unit heater is designed to provide safety, comfort, and efficiency to industrial, commercial, and residential buildings. The Reznor UDXC boasts a TCORE2 heat exchanger, featuring titanium-stabilized aluminized steel for long-lasting performance and efficient heating.


Included

  • Reznor UDXC 175,000 BTU Low Static Axial Fan Convertible Gas-Fired Unit Heater; Model UDXC-175

Built to last and look great. The UDXC also features a durable, two-tone, scratch-resistant paint finish. Clean rounded corners and edges and hidden fasteners enhance its modern design, making it ideal for industrial or residential use.

Standard Features

  • 175,000 BTU
  • Uses Axial Propeller Fan
  • 83% Thermal Efficiency
  • Field convertible to separated combustion
  • Sealed control compartment houses all electrical components
  • TCORE2 titanium stabilized aluminized steel heat exchanger
  • Vibration/noise isolated fan and venter motors
  • Certified for commercial/industrial heating applications

Product Note

Replaces UDX-175 / UDZ-175 / UDAP-175 / UDAS-175

More Information
Reznor UDXC 175,000 BTU Natural Gas Unit Heater, Propeller Fan, Separated Combustion Convertible - Replaces UDX-175 / UDZ-175
FeatureSpec
SKUUDXC-175
Weight (in lbs)221
Brand/ManufacturerReznor
ReplacesUDX-175
UPC663132524891
Furnace Efficiency / AFUE 80-85%
Heating BTU175,000 BTU
Maximum CFM2242
Decibel Level (dBA)52dB at 15ft
Motor RPM1050 Fan motor speed
Horsepower1/4 - Totally-enclosed fan motor horsepower
Watt392 Watts
Efficiency83%
Electrical115 Volt 1 Phase 60 Hertz
PhaseSingle Phase
Amperage Requirement3.8 Amps
Operating ModeHeating
Connection1/2" NG/LP Connection to Gas Valve
Fuel TypeNatural Gas
Height20 1/8"
Width38 3/16"
Depth48 7/16"
Warranty9 Year Heat Exchanger, Burner, and Flue Collection Box Assembly; 4 Year All Electrical and Mechanical Components
Resources You will need Adobe Acrobat Reader to view PDF documents.
Safety InformationPROPOSITION 65 WARNING

Customers Say

Across multiple installations, owners report fast heat-up times and strong output, including raising a 950 sq ft garage from 35°F to 70°F in 15–20 minutes, heating a 60x40x16 shop from 58°F to 70°F in 35 minutes, maintaining 60°F at -11°F outdoors, and warming 35,000 cubic feet in under 10 minutes. Installations are frequently described as straightforward—sometimes completed in about four hours or by reusing existing mounts when replacing older Reznor units lasting nearly 20 years—though minor issues included an incorrect conversion kit and one poor delivery drop-off.

AI Generated from the text of customer reviews

Top reviews
  1. Reznor UDX 60K
    Quality
    100%
    Service
    100%
    Price
    100%
    The unit was packaged well, and the installation was straightforward. It’s heated my workshop in Northern Michigan for three seasons now, and it’s been flawless.

    Review by

    Posted on

  2. UDX200
    Quality
    100%
    Service
    100%
    Price
    100%
    Great looking heaters, and performs wells. great service.

    Review by

    Posted on

  3. Great support easy transaction
    Quality
    100%
    Service
    100%
    Price
    100%
    Great support and quality product will buy fromagain

    Review by

    Posted on

  4. Reznor 60K BTU
    Quality
    100%
    Service
    100%
    Price
    100%
    HVAC Direct delivered on time and unit was incredibly packaged for freight. The unit itself is performing quite well in an uninsulated garage. Keeps everything from freezing. I could not be happier with this purchase and my purchase experience. I will definitely purchase from HVAC Direct when its time to heat my 30x40 barn.

    Review by

    Posted on

  5. Outstanding product
    Quality
    100%
    Service
    100%
    Price
    100%
    Got a 46x60 shop with 16ft ceilings the reznor 150,000 btu heats it up fast runs quiet totally surprised how this unit performs

    Review by

    Posted on

  6. Fast delivery, great price, excellent packaging with zero damage. Easy to install.
    Quality
    100%
    Service
    100%
    Price
    100%
    Ordered to replace an old UDAP 45. Basically the same but taller. Fit fine as a hanging unit in the garage. Quieter and warmer output than the old one. Pretty much just unhooked the old one, unmounted it and mounted the new one with the same bolts, reattached connections with a slight modification to the venting. Free shipping and it still got here in less than a week. Overall, great experience with HVACDirect and the price was the lowest I could find.

    Review by

    Posted on

  7. Great heater
    Quality
    100%
    Service
    100%
    Price
    100%
    Easy installation, quiet and works very well!

    Review by

    Posted on

  8. Great purchase
    Quality
    100%
    Service
    100%
    Price
    100%
    We just installed this unit today and it heated my shop up from 58degs. To 70degs. In 35 minutes. The shop is 60x40x16 high.

    Review by

    Posted on

See more reviews
Customer Questions
If the green light is green flashing, what does that mean?
There are a variety of things that this could indicate. Refer to Table 26 on page 59 of the Reznor UDXC Installation and Maintenance Manual. If you have any further questions, please feel free to give us a call! Thanks.
What type of venting do these unit heaters require? B-vent or PVC?
These units require Category I (B-vent) for vertical venting through the roof, or Category III for venting horizontally through side walls. The exhaust on these units exceeds a temperature that would allow for PVC Venting. If you have any further questions, please feel free to give us a call. Thanks!
Can I use PVC pipe for the combustion air intake?
Reznor does not approve the use of PVC pipe for combustion air intake. Reznor only approves the use of the concentric venting, which is not compatible with PVC. Attempting to vent non-concentric can lead to pressure imbalances which would cause the pressure switch to intermittently turn the unit off. If you have any further questions, please feel free to give us a call. Thanks!
What is the max length for B-vent to exhaust through the roof?
Please refer to pages 34-35 of the installation manual for vertical venting size constraints. This installation manual is linked on the Product Specifications tab for this unit and listed in the Resources section. If you have any further questions, please feel free to give us a call. Thanks!
On the 175,000 BTU reznor unit heaters 3H917NA, what is the gas line psi requirement?
    Hello, thank you for reaching out. The gas supply pressure must not exceed 1/2 psi (14 inches water column) at the unit's gas valve. If you have additional questions, please feel free to reach out over the phone to our Customer Service line at 1-888-901-5460. Have a great rest of your day.    