The Trane 5TWA4036A4 is a 3-ton commercial split heat pump condenser designed to provide dependable heating and cooling for small commercial applications. Combining a 36,000 BTU/h nominal cooling capacity outdoor heat pump condenser with compatible indoor air-handling equipment, this split system helps deliver year-round comfort while providing flexible installation options for commercial applications. The 5TWA4036A4 uses 460V, three-phase, 60 Hz electrical service and R-454B refrigerant.
The 5TWA4036A4 is a split-system heat pump designed to provide both heating and cooling operation. It uses one ClimaTuff® scroll compressor with single-stage operation and an expansion valve for refrigerant control. Trane's published AHRI rating conditions include high-temperature heating at 47°F outdoor dry-bulb temperature and low-temperature heating at 17°F outdoor dry-bulb temperature.
The 5TWA4036A4 provides 36,000 BTU/h of nominal cooling capacity. The outdoor unit uses a single-stage ClimaTuff® scroll compressor, a direct-drive propeller outdoor fan, and a Spine Fin™ outdoor coil. Its published A-weighted sound power level is 76 dB(A), rated in accordance with AHRI Standard 270.
The 5TWA4036A4 uses R-454B refrigerant and an expansion valve for refrigerant control. The outdoor unit is factory supplied with approximately 5 lb. 10 oz. of R-454B refrigerant. Trane specifies 10°F subcooling as the charging specification and notes that proper system charge should always be verified according to the unit nameplate and applicable charging procedure.
The 5TWA4036A4 is configured for 460V, three-phase, 60 Hz power and has a published minimum branch circuit ampacity of 6.8 amps with a maximum branch circuit protection rating of 15 amps. The outdoor unit uses a 3/4-inch O.D. gas connection and a 5/16-inch O.D. liquid connection. Trane identifies 25-, 30-, 35-, and 50-foot line sets as available options and recommends consulting its refrigerant piping guidance for applicable line-length and lift requirements.
The 5TWA4036A4 uses single-stage heat pump operation with a direct-drive, single-speed outdoor fan and expansion-valve refrigerant control. The optional TAYASCT501A anti-short-cycle timer is a solid-state timing device designed to prevent compressor recycling until five minutes have elapsed after a satisfied call or power interruption. Trane identifies the timer for applications including commercial installations and long line sets.
The Trane 5TWA4036A4 is part of Trane's 5TWA4 three-phase single-stage heat pump family covering 3- to 5-ton nominal capacities. The 5TWA4036A4 is the 36,000 BTU/h model with 460V three-phase power, making it suitable for compatible small commercial applications where this electrical configuration is required.
The 5TWA4036A4 provides access to optional accessories intended to address specific installation and service requirements. Available options include the TAYASCT501A anti-short-cycle timer, BAYISLT101 rubber isolator kit, BAYECMT004 extreme-condition mounting kit, BAYSDEN003 sound enclosure, BAYCCHT302 crankcase kit, BAYKSKT263 start kit, BAYSEAC001 seacoast kit, BAYLOAM107 low-ambient kit, and TAYSVPANL3343AA service valve panel cover. The rubber isolator kit is designed to minimize sound transmission through the mounting structure, while the extreme-condition mounting kit is intended for high-wind areas and commercial rooftop installations.
Warranty coverage for the Trane 5TWA4036A4 should be confirmed using the applicable current Trane warranty documentation for the installation and equipment configuration. The product and submittal documentation does not specify warranty terms for this model.
Experience dependable year-round heating and cooling with the Trane 5TWA4036A4 3-ton commercial split heat pump condenser. Combining a single-stage ClimaTuff® scroll compressor, Spine Fin™ outdoor coil, R-454B refrigerant, expansion-valve refrigerant control, and 460V three-phase electrical configuration, the 5TWA4036A4 provides a flexible heat pump solution for compatible small commercial applications.